Cast Resin Encapsulated Ring Type CT

TECHNICAL DATA

  • Epoxy or Polyurethane Resin Moulded Window Type
  • For Indoor Measuring/Protection Use
  • Highest System Voltage : 0.72kV, 3.6kV, 7.2kV, 12kV
  • Rated Primary Current: 50A-6000A
  • Rated Secondary Current: 1A or 5A
  • Rated Output/Burden : 2.5VA-40VA
  • Accuracy Class: For metering CTs; 0.2s, 0.2, 0.5, 0.5s, 1.0, 3.0
  • For Protection CTs; 5P5, 5P10, 5P15, 5P20, 5P30, 10P5,10P10, 10P15, 10P20, 10P30, PS(X)
  • Rated Frequency: 50/60 Hz
  • Rated Short-time thermal current (0.5s), Ith : max. 50kA
  • Rated Dynamic Current : 2.5 × Ith
  • Standards/Directives : IEC-60044-1/IEC-61869-2
qwe
xs

Cast Resin Rectangular/Round Window Type CT

TECHNICAL DATA

  • Epoxy or Polyurethane Resin Moulded Rectangular/Round Window Type
  • For Indoor Measuring/Protection Use
  • Highest System Voltage : 0.72KV,3.6KV,7.2KV,12
  • Test Voltages : 3/8 kV
  • Rated Primary Current: 50A-6000A
  • Rated Secondary Current: 1A or 5A
  • Rated Output/Burden : 2.5VA-40VA
  • Accuracy Class: For metering CTs; 0.2s, 0.2, 0.5, 0.5s, 1.0, 3.0
  • For Protection CTs; 5P5, 5P10, 5P15, 5P20, 5P30, 10P5,10P10, 10P15, 10P20, 10P30, PS(X)
  • Rated Frequency: 50/60 Hz
  • Rated Short-time thermal current (0.5s), Ith : max. 50kA
  • Rated Dynamic Current : 2.5 × Ith
  • Standards/Directives : IEC-60044-1/IEC-61869-2
4
3

Plastic Moulded Case Ring Type CT

TECHNICAL DATA

  • ABS/Polycarbonate Plastic Moulded Window Type
  • For Indoor Measuring/Protection Use
  • Highest System Voltage : 0.72kV
  • Test Voltages : 3/8 kV
  • Rated Primary Current: 50A-4000A
  • Rated Secondary Current: 1A or 5A
  • Rated Output/Burden : 1.5VA-40VA
  • Accuracy Class: For metering CTs; 0.2s, 0.2, 0.5, 0.5s, 1.0, 3.0
  • For Protection CTs; 5P5, 5P10, 5P15, 5P20, 5P30, 10P5,
    10P10, 10P15, 10P20, 10P30, PS(X)
  • Rated Frequency: 50/60 Hz
  • Rated Short-time thermal current (1s), Ith : 80 × In
  • Rated Dynamic Current : 2.5 × Ith
  • Standards/Directives : IEC-60044-1/IEC-61869-2
Img#3
2

Plastic Moulded Case Rectangular CT

TECHNICAL DATA

  • ABS/Polycarbonate Plastic Moulded Window Type
  • For Indoor Measuring/Protection Use
  • Highest System Voltage : 0.72KV
  • Test Voltages : 3/8 kV
  • Rated Primary Current: 50A-4000A
  • Rated Secondary Current: 1A or 5A
  • Rated Output/Burden : 1.5VA-40VA
  • Accuracy Class: For metering CTs; 0.2s, 0.2, 0.5, 0.5s, 1.0, 3.0
  • For Protection CTs; 5P5, 5P10, 5P15, 5P20, 5P30, 10P5,10P10, 10P15, 10P20, 10P30, PS(X)
  • Rated Frequency: 50/60 Hz
  • Overload Withstand: 1.2 times rated current continuously
  • Rated Short-time thermal current (0.5s), Ith : 80 × In
  • Rated Dynamic Current : 2.5 × Ith
  • Standards/Directives : IEC-60044-1/IEC-61869-2
3
4

Tape Wound Ring Type CT

TECHNICAL DATA

  • Tape Insulated (Polyester, Acetone, PVC or Cotton)
  • For Indoor Measuring/Protection Use
  • Highest System Voltage : 0.72kV
  • Test Voltages : 3/8 kV
  • Rated Primary Current, In: 50A-4000A
  • Rated Secondary Current: 1A or 5A
  • Rated Output/Burden : 1.5VA-40VA
  • Accuracy Class: For metering CTs; 0.2s, 0.2, 0.5, 0.5s, 1.0, 3.0
  • For Protection CTs; 5P5, 5P10, 5P15, 5P20, 5P30, 10P5, 10P10, 10P15, 10P20, 10P30, PS(X)
  • Rated Frequency: 50/60 Hz
  • Rated Short-time thermal current (0.5s), Ith : 60 × In
  • Rated Dynamic Current : 2.5 × Ith
  • Standards/Directives : IEC-60044-1/IEC-61869-2
1
2

Tape Wound Rectangular CT

TECHNICAL DATA

  • Tape Insulated (Polyester, Acetone, PVC or Cotton)
  • For Indoor Measuring/Protection Use
  • Highest System Voltage : 0.72KV
  • Test Voltages : 3/8 kV
  • Rated Primary Current, In: 50A-4000A
  • Rated Secondary Current: 1A or 5A
  • Rated Output/Burden : 1.5VA-40VA
  • Accuracy Class: For metering CTs; 0.2s, 0.2, 0.5, 0.5s, 1.0, 3.0
  • For Protection CTs; 5P5, 5P10, 5P15, 5P20, 5P30, 10P5, 10P10, 10P15, 10P20, 10P30, PS(X)
  • Rated Frequency: 50/60 Hz
  • Rated Short-time thermal current (0.5s), Ith : 60 × In
  • Rated Dynamic Current : 2.5 × Ith
  • Standards/Directives : IEC-60044-1/IEC-61869-2
3-2
4